MOELLER ESR4-NO-21 (18815873 B081) Dual Channel Safety Relay

₨ 0

The Moeller (now Eaton) ESR4-NO-21 is a 24V AC/DC dual-channel safety relay designed to monitor emergency stop buttons and safety guard doors in industrial machinery. The code 18815873 is the internal manufacturing/serial batch identifier printed on the housing, while B081 denotes a production revision or date code. 

Key Specifications

  • Operating Voltage. Rated at 24V AC/DC via supply terminals A1 and A2. 
  • Input Configuration. Supports dual-channel emergency stop or safety door monitoring (terminals S21/S22) with reset button monitoring (terminal S34). 
  • Output Contacts. Provides 2 normally open (NO) safety enabling paths and 1 normally closed (NC) auxiliary/signaling contact. 
  • Contact Ratings. Rated for 250V / 2.5A general switching, or 230V / 6A under AC-15 and 24V DC / 6A under DC-13 utilization categories. 
  • Safety Compliance. Conforms to IEC/EN 60204-1 for Stop Category 0 and Category 1 protection paths with positively guided relay contacts.